The Nitrogen fire fighting system is commonly employed in power transformers at Power substations. The Nitrogen Injection Fire Protection System (NIFPS) protects against explosions or potential oil fires in the case of arcing caused by internal or external faults in transformers' oil tanks. If you need more info call to our company number or you can send the message on the whatsApp
Fire extinction period from commencement of nitrogen injection | 30 secs.(Max.) |
Fire extinction period from activation of system | 3 minutes (Max.) |
Fire detector’s (quartz bulb) heat sensing temperature | 141oC |
Heat sensing area per detector | Up to radius of 800 mm |
Transformer Conservator Isolation valve setting | 60 ltr / min (Minimum) |
Capacity of nitrogen Generator | 68 ltr (Minimum) with N2 storage tank for 10 m3 Nitrogen gas. |
Power supply | 230 VAC |
i) Low investment cost as compared to other conventional system.
ii) Very low post fire and no secondary damages.
iii) Minimum maintenance and running cost.
iv) No climatic effects.
v) Suitable for indoor / outdoor installation.
vi) Minimum space requirement.
vii) Multi signals for activation, eliminates false alarms.
viii) Allows system testing on operational transformer not possible with conventional fire
system.
ix) No moisture absorbing in inside the transformer due to presence of nitrogen.
x) Great saving in cost, due to absence of moisture.
xi) Fully automatic, unattended and a fool proof system.
xii) It can be operated manually / automatically, local / remote control.
xiii) No water reservoir or major civil work required.
xiv) Prevents transformer explosion ensuring system remains functioning.
xv) Prevention of unplanned outages.
xvi) Considerable savings.
xvii) Improves overall power system reliability.